Insulation : PVC or XLPE (Cross Linked Polyethylene)
Bedding : Extruded PVC
Armour : Galvanised Steel Wire Armour
Sheath : PVC Black
Conductor : Stranded or Solid Plain Annealed Copper.
Application : Designed for use in mains supply electricity. These cables are provided with mechanical protection are therefore suitable for external use and direct burial.
Technical Data : Voltage: 600/1000V,Temperature range: 0oC to +90oC
Relevant Standards :
Conductor :To BS6360
Armour :To BS442
Sheath :To BS6746 Type G.
Core Identification :
2 Cores : Blue, Brown
3 Cores : Brown, Black, Grey
4 Cores : Blue, Brown, Black, Grey
5 Cores (6mm and below) :White Insulation With Black Numbers
5 Cores (10mm and above) : Brown, Blue, Black, Grey and G/Y

XLPE / PVC / AWA / PVC (Copper) BS5467
Single Core Plain annealed copper conductor, XLPE insulated / PVC extruded bedded / Aluminium wire armoured / PVC sheathed. 600 / 1000 volts grade to BS5467

Size SQ. MM Maximum Diameter over Conductor MM) RT Of Insulation MM Diameter over Core MM RT of Bedding MM Diameter over Bedding MM Diameter of Armour Wire MM Diameter over Armour MM Approx Overall Diameter MM Weight KG / KM
50 8.90 1.0 10.9 0.8 12.6 0.9 14.5 17.5 708
70 10.70 1.0 12.9 0.8 14.6 1.25 17.1 20.2 970
95 12.60 1.1 14.8 0.8 16.4 1.25 19.0 22.3 1240
120 14.21 1.2 16.7 0.8 18.4 1.25 21.0 24.2 1510
150 15.75 1.4 18.6 1.0 20.7 1.6 24.0 27.4 1930
185 17.64 1.6 20.9 1.0 23.0 1.6 26.3 30.0 2330
240 20.25 1.7 23.8` 1.0 25.9 1.6 29.2 32.8 2900
300 22.68 1.8 26.4 1.0 28.5 1.6 31.8 35.6 3530
400 25.65 2.0 29.8 1.2 32.3 2.0 36.4 40.4 4690
500 28.80 2.2 33.3 1.2 35.8 2.0 39.9 44.2 5740
630 32.76 2.4 37.7 1.2 40.2 2.0 44.3 48.8 7150
800 37.05 2.6 42.4
1.4
45.3 2.5 50.4 55.4 9070
1000 41.60 2.8 47.3 1.4 50.2
2.5
55.3 60.6 11120

MultiCore Armoured (Copper)
XLPE / PVC / SWA / PVC (copper) BS5467 Plain annealed copper conductor, XLPE insulated / PVC extruded bedded / Steel Wire armoured / PVC sheathed. 600 / 1000 volts grade to BS5467.

Two Core : 6942X
Size SQ. MM Class of Conductor RT Of Insulation MM Diameter over Bedding MM Diameter of Armour Wire MM Diameter over Armour MM Approx Overall Diameter MM Weight KG / KM
1.5 2 1.0 20.3 1.6 23.6 27.3 1560
2.5 2 1.0 22.7 1.6 26.0 29.7 1930
4 2 1.0 26.3 1.6 29.6 33.5

2530


Twenty Seven Core : 694 / 27X
Size SQ. MM Class of Conductor RT Of Insulation MM Diameter over Bedding MM Diameter of Armour Wire MM Diameter over Armour MM Approx Overall Diameter MM Weight KG / KM
1.5 2 1.0 20.7 1.6 24.0 27.9 1630
2.5 2 1.0 23.2 1.6 26.5 30.2 2050
4 2 1.0 26.9 1.6
30.2
34.4 2740

Thirty Core : 694 / 30X
Size SQ. MM Class of Conductor RT Of Insulation MM Diameter over Bedding MM Diameter of Armour Wire MM Diameter over Armour MM Approx Overall Diameter MM Weight KG / KM
1.5 2 1.0 21.5 1.6 24.8 28.5 1730
2.5 2 1.0 24.1 1.6 27.4 31.3 2200

Thirty Seven Core : 694 / 30X
Size SQ. MM Class of Conductor RT Of Insulation MM Diameter over Bedding MM Diameter of Armour Wire MM Diameter over Armour MM Approx Overall Diameter MM Weight KG / KM
1.5 2 1.0 23.3 1.6 26.6 30.6 1970
2.5 2 1.0 26.1 1.6 29.4 33.8 2540
4 2 1.2 31.0 2.0 35.4 39.6 -

Forty Core : 694 / 40X
Size SQ. MM Class of Conductor RT Of Insulation MM Diameter over Bedding MM Diameter of Armour Wire MM Diameter over Armour MM Approx Overall Diameter MM Weight KG / KM
1.5 2 1.0 24.3 1.6 27.6 31.5 2080
2.5 2 1.0 27.7 1.6 31.8 35.9 2970

Forty Eight : 694 / 48X
Size SQ. MM Class of Conductor RT Of Insulation MM Diameter over Bedding MM Diameter of Armour Wire MM Diameter over Armour MM Approx Overall Diameter MM Weight KG / KM
1.5 2 1.0 26.7 1.6 30.0 33.9 2390
2.5 2 1.0 30.4 2.0 - - -