6942X Series Power Cables
SWA Armoured Cables
Insulation : PVC or XLPE (Cross Linked Polyethylene)
Bedding : Galvanised Steel Wire Armour
Sheath : PVC Black
Conductor : Stranded or Solid Plain Annealed Copper.
Application : Designed for use in mains supply electricity. These cables are provided with mechanical protection are therefore suitable for external use and direct burial.
Technical Data : Voltage: 600/1000V,Temperature range: 0oC to +90oC
Relevant Standards :
Conductor : To BS6360
Armour : To BS442
Sheath : To BS6746 Type G.
Core Identification :
2 Cores :Blue, Brown
3 Cores :Brown, Black, Grey
4 Cores :Blue, Brown, Black, Grey
5 Cores (6mm and below) :White Insulation With Black Numbers
5 Cores (10mm and above) :Brown, Blue, Black, Grey and G/Y
Write to Us
XLPE / PVC / AWA / PVC (Copper) BS5467
Single Core Plain annealed copper conductor, XLPE insulated / PVC extruded bedded / Aluminium wire armoured / PVC sheathed. 600 / 1000 volts grade to BS5467
Two Core : 6942X
Size SQ. MM | Class of Conductor | RT Of Insulation MM | Diameter over Bedding MM | Diameter of Armour Wire MM | Diameter over Armour MM | Approx Overall Diameter MM | Weight KG / KM |
---|---|---|---|---|---|---|---|
1.5 | 2 | 1.0 | 20.3 | 1.6 | 23.6 | 27.3 | 1560 |
2.5 | 2 | 1.0 | 22.7 | 1.6 | 26.0 | 29.7 | 1930 |
4 | 2 | 1.0 | 26.3 | 1.6 | 29.6 | 33.5 | 2530 |
Twenty Seven Core : 694 / 27X
Size SQ. MM | Class of Conductor | RT Of Insulation MM | Diameter over Bedding MM | Diameter of Armour Wire MM | Diameter over Armour MM | Approx Overall Diameter MM | Weight KG / KM |
---|---|---|---|---|---|---|---|
1.5 | 2 | 1.0 | 20.7 | 1.6 | 24.0 | 27.9 | 1630 |
2.5 | 2 | 1.0 | 23.2 | 1.6 | 26.5 | 30.2 | 2050 |
4 | 2 | 1.0 | 26.9 | 1.6 | 30.2 | 34.4 | 2740 |
Thirty Core : 694 / 30X
Size SQ. MM | Class of Conductor | RT Of Insulation MM | Diameter over Bedding MM | Diameter of Armour Wire MM | Diameter over Armour MM | Approx Overall Diameter MM | Weight KG / KM |
---|---|---|---|---|---|---|---|
1.5 | 2 | 1.0 | 21.5 | 1.6 | 24.8 | 28.5 | 1730 |
2.5 | 2 | 1.0 | 24.1 | 1.6 | 27.4 | 31.3 | 2200 |
Thirty Seven Core : 694 / 30X
Size SQ. MM | Class of Conductor | RT Of Insulation MM | Diameter over Bedding MM | Diameter of Armour Wire MM | Diameter over Armour MM | Approx Overall Diameter MM | Weight KG / KM |
---|---|---|---|---|---|---|---|
1.5 | 2 | 1.0 | 23.3 | 1.6 | 26.6 | 30.6 | 1970 |
2.5 | 2 | 1.0 | 26.1 | 1.6 | 29.4 | 33.8 | 2540 |
4 | 2 | 1.2 | 31.0 | 2.0 | 35.4 | 39.6 | - |
Forty Core : 694 / 40X
Size SQ. MM | Class of Conductor | RT Of Insulation MM | Diameter over Bedding MM | Diameter of Armour Wire MM | Diameter over Armour MM | Approx Overall Diameter MM | Weight KG / KM |
---|---|---|---|---|---|---|---|
1.5 | 2 | 1.0 | 24.3 | 1.6 | 27.6 | 31.5 | 2080 |
2.5 | 2 | 1.0 | 27.7 | 1.6 | 31.8 | 35.9 | 2970 |
Forty Eight : 694 / 48X
Size SQ. MM | Class of Conductor | RT Of Insulation MM | Diameter over Bedding MM | Diameter of Armour Wire MM | Diameter over Armour MM | Approx Overall Diameter MM | Weight KG / KM |
---|---|---|---|---|---|---|---|
1.5 | 2 | 1.0 | 26.7 | 1.6 | 30.0 | 33.9 | 2390 |
2.5 | 2 | 1.0 | 30.4 | 2.0 | - | - | - |